Engineering manual - UniSAB III 1.10.8
218/346
001930 en 2021.06
9: Oil flow open min
5 to 70% [10%]
This parameter is used when the
oil flow control
function is enabled. It defines the valve opening degree
at minimum speed.
The
Oil flow open min
parameter is set automatically between 5% and 40%, when the
Motor RPM min
parameter is changed, given as:
Oil flow open min
= -10% + 20% x
Motor RPM min
/1000
The
oil flow open min
parameter is used for the
oil flow control
function; see detailed description under
7: Oil flow control
above.
10: Balance pressure reduction
No
Yes
Select
Yes
for compressor types SAB 193 H–355 H and SAB 273 S to enable
balance pressure reduc-
tion
supervision.
The
balance pressure reduction
is supervised to avoid too high balance piston pressure.
See detailed description in subsections 2.2.40 to 2.2.43.
Note:
The low alarm and shutdown supervision is only active when the AUX function
At bal. cap.
is ac-
tive, i.e. when the AUX output is OFF, and with a delay of 5 sec. See subsection
11: Sep. Vel. Ref.
0.00-10.00
Separator velocity reference
is calculated in the programs CoolWare or COMP 1 when calculating the
unit based on running conditions. Enter the COMP 1 or CoolWare result here. This parameter is used in
connection with the capacity limitation
Separator velocity
. See section
.
Note:
When using the Comp1 or Comp2 program this value is named
Oil separator load
and it is dis-
played in percent.
12: Sep. Vel. CR
Separator velocity compression ratio
is calculated in the programs CoolWare or COMP 1 when calculat-
ing the unit based on running conditions. Enter the COMP 1 or CoolWare result here. This parameter is
used in connection with the capacity limitation
Separator velocity
. See section
13: Sep. temp. control
This setting enables
Oil separator temperature control
and supervision for the following screw compres-
sor types: