Engineering manual - UniSAB III 1.10.8
178/346
001930 en 2021.06
Separator velocity (screws)
Max. sep. cap. load
is the calculated value in % for the maximum true capacity load allowed at current
running conditions. When this value is between 100 and 102% the capacity inhibit function is activated.
When the value is below 100% the capacity force unload is activated.
Max. cap. slide pos.
is the calculated value in % for the maximum mechanical capacity load allowed at
current running conditions. This value which will be between 0% and 100% is the limiting value used
when the
capacity force unload
function is active.
Pressure Ratio
is the calculated pressure ratio = P
disch
/P
suct
.
K. Factor
is the refrigerant constant, κ (Kappa).
System Compr. Ratio
is the calculated system compression ratio.
Syst. Sep. Vel. Ratio
is the calculated system separator velocity ratio.
Utilisation Number
is the calculated utilisation ratio for the separator at current running conditions. Eg
a value of 1.00 means that the separator is fully loaded and that the capacity-inhibit function is activated.
For more information, see subsection
Misc. functions
This picture includes five items: