Engineering manual - UniSAB III 1.10.8
96/346
001930 en 2021.06
Compressor control and surveillance
superheating of the plant must be entered as
Set point 2
in the picture
Control values/Suction/Super-
heat/Control
if differing from the above factory value.
Adjusting range: -10 - +30
°
C
By adjusting
Set point 2
for
Suction superheat
upwards or downwards, the limit curve will be dislocated
accordingly.
If
Set point 2
is set at -10
°
C, the limit curve will be dislocated so much upwards that the limiting function
will be disabled.
Liquid level limiter (reciprocating compressors)
This capacity limiting function for ChillPAC Mk 3 works for all reciprocating compressors that do not use
the
Filter diff. pressure
function.
The limiter will reduce compressor capacity (3%/sec, up to 33-50%) as long as the liquid level is high in
the evaporator. When the liquid level is back to normal, and after the
Liquid level delay
has timed out,
the compressor is allowed to increase capacity.
Separator velocity (screw compressors)
For all screw compressors a capacity limiting function for
high separator gas velocity
can be activated. It
will limit the compressor capacity to a calculated limit based on the current running conditions. To acti-
vate the limiter, two values calculated from the
Refrigeration Plant Computation program
are required:
•
Actual separator velocity limit reference
•
The compression ratio at which the above value was calculated.
The high capacity limit for the separator is calculated by means of the measured compression ratio and
the two mentioned reference values. When the limiter inhibit function is active (i.e. capacity cannot be in-
creased) the text
Running overload
is shown in the status field on the display.
The
Alarm
picture reads:
Limiting high separator flow
. When the limiter force-unload function is active (i.
e. capacity will actively be decreased) the status text
Running overload
is shown in the status field on
the display.
The text in the
Alarm
picture reads:
Limiting high separator flow
.
The set up values for the limiter are entered in the
Setup/Configuration/Oil system
picture.
Min.
Max.
Sep.vel.ref
0.49
0.00
10.00
Sep.vel.cr
4.72
0.00
100.00
The calculated (intermediate) values for the separator limiting function are shown in the
Diagnosis
pic-
ture
Service/Diagnosis/Software/Separator Velocity
.