Engineering manual - UniSAB III 1.10.8
278/346
001930 en 2021.06
UniSAB III (boot) and communication set-up
8.3.1
Uploading new software version
Place the following files for e.g. software version 1.0.6.5, in a library with the following path on the flash
card: E:\UniSABIII\updates\1_0_6_5:
•
UniSABIII_1065.strip - (program application, not visible in the file overview)
•
ResourceBundles – (language file library)
•
Vfd.dat - (data information for frequency drive)
Insert the flash card in UniSAB III and follow the instruction described in section
and
. Update to upload the software update.
If the file version on the SD card is newer than the present software version, UniSAB III will ask if the
software version should be updated when you insert the SD card and restart UniSAB III (i.e. pressing
,
,
or power off/on).
First you will be prompted to accept.
If you answer
Yes
, updating (uploading) to version 1.0.6.9 will take place.
UniSAB III is now updated to version 1.0.6.9 (including the 18 language files, VFD.dat and optional con-
figuration files on the SD card). Now restart UniSAB III to make the software change take effect.
F2
F3
F4
Summary of Contents for SABROE Unisab III Control
Page 1: ...UniSAB III control Version 1 10 8 Engineering manual EN...
Page 2: ......