Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
31/346
1.2.6
Changing set values
This example illustrates how to change set values such as alarm limits, shutdown limits, set points and
timer starting value. First you must position the (dark) cursor on the value you want to change. In this ex-
ample it is the
Low shutdown limit for suction pressure
. Proceed as follows:
In the menu illustrated below, move the cursor to
Control values
with the
and
keys. Press
to go
to
Suction
and once again to go to
(suction) Values
and again to get to the
Suction/Values
picture.
In the next picture, move the cursor down to
Suction pressure
with the
key and then press
/LIMITS
to get to the
(suction) limits
picture.
Press
four times to get to the
Low shutdown value
.
To change the
low shutdown limit
, press
.
You must enter a password to continue. To change this low shutdown limit you must choose a
Superuser
(or higher level) password.
F2