Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
229/346
6.4.14
Maximum movement of capacity slide
Table 51 is used for the calculation of
Manual zero
in the
Compressor block configuration
.
Regulator type
Max. movement
of capacity slide
Evaporating
temp.
R717/R22
Length of
spacer block
Mechanical
zero
Manual zero
SAB 110 SM
84.5
< -20
°
C
22
No
0%
SAB 110 SF
SAB 110 LM
96
> -20
°
C
None
No
*
Factor 0%
SAB 110 LF
SAB 128 HM Mk 2
126
< -20
°
C
31.5
No
0%
SAB 128 HF Mk 2
SAB 128 HM Mk 3
> -20
°
C
None
No
*
Factor 0%
SAB 128 HF Mk 3
SAB 163 M Mk 1, Man Vi
160
< -20
°
C
38.5
No
0%
SAB 163 F Mk 1, Man Vi
SAB 163 HM Mk 2, Man Vi
SAB 163 HF Mk 2, Man Vi
> -20
°
C
None
No
*
Factor 0%
SAB 163 HM Mk 3, Man Vi
SAB 163 HF Mk 3, Man Vi
SAB 163 HM Mk 2, Aut Vi
160
< -20
°
C
38.5
Yes
24%
SAB 163 HF Mk 2, Aut Vi
SAB 163 HM Mk 3, Aut Vi
> -20
°
C
None
No
*
Factor 0%
SAB 163 HF Mk 3, Aut Vi
SAB 202 SM, Man Vi
245
All
None
**
No
*
Factor 0%
SAB 202 SF, Man Vi
SAB 202 SM, Aut Vi
SAB 202 SF, Aut Vi
SAB 202 LM, Man Vi
317
All
None
**
No
*
Factor 0%
SAB 202 LF, Man Vi
SAB 202 LM, Aut Vi
SAB 202 LF, Aut Vi
SAB 283 L
314
Not
relevant
Not
relevant
Not
relevant
Not
relevant
SAB 283 E
391
SAB 355 L
350
SAB 330 S
262
Not
relevant
Not
relevant
Not
relevant
Not
relevant
SAB 330 L
371
SAB 330 E
480
* If inserting a different value than the default factory set value (0%), the automatic zero setting is eliminated.
Therefore, only insert a value different from 0% after contacting your Sabroe representative.
** If inserting a different value than “No”, the automatic zero setting is eliminated.
Therefore, only insert a value different from “No” after contacting your Sabroe representative.
Table 51: Maximum movement of capacity slide