Compressor control and surveillance
Pump down
To the compressor stop sequence is added a “Pump down function”. The expansion valve closes and
the compressor keeps running until the suction pressure is below the
Pump down Set point
[°C] limit or
until the
Pump down
stop timer has run out, whichever comes first.