Engineering manual - UniSAB III 1.10.8
292/346
001930 en 2021.06
UniSAB III (boot) and communication set-up
8.7
Software tools
8.7.1
SabHMI remote user interface
Connecting the SabHMI interface to the UniSAB III panel
If connecting directly from the UniSAB III panel to the PC, use a crossed LAN cable. The PC must be set
to a specific IP address matching the address of the UniSAB III on the first three segments. Segment 4
must be different. The Subnet mask must be the exact same on the PC as on the UniSAB III.
If UniSAB III and the PC are both connected to a LAN network, the PC can be set to obtain the IP ad-
dress automatically but the Subnet mask on the UniSAB III panel must be set to the same one used on
the LAN network.
Start the UniSAB III HMI simulator. Find the menu
Setup/Session/Remote Connect
. Adjust the IP ad-
dress to be the same as the one in the UniSAB III panel you wish to connect to. Please note that the IP
address is divided into 4 sections (IP no. 1, 2, 3 and 4).
When the IP address is set, scroll down to the line
Remote Connect
and select
Remote
. Now communi-
cation between the HMI simulator and the UniSAB III panel is established and the last line reads
Con-
nected to the specific address
.
With SabHMI you can operate the connected UniSAB III remotely as if you were operating UniSAB III it-
self. Operation is carried out the exact same way; you have the same display and can press the keys
with your mouse.
From UniSAB III version 1.0.5.0, the SabHMI application can be started directly with an IP number as
parameter. Using the string: /REM: xxx. xxx. xxx. xxx as a parameter in the windows shortcut makes
SabHMI connect remotely to the UniSAB III with IP number xxx.xxx.xxx.xxx.
The shortcut target line may look like this: "C: \Program Files \YORK \UniSABIII_1056 \Win32HMI. exe"
/REM:10.63.129.34. In this example SabHMI will connect remotely to the UniSAB III with IP number
10.63.129.34.
From version 1.0.7.0 the name of file map where program and data files are installed is changed from
\YORK\ to \JCI\. The shortcut target line may now look like this: "C:\Program Files\JCI\UniSABIII_1076
\Win32HMI.exe" /REM:10.63.129.34.
From version 1.0.8.0 the file map where the data (xml) files are installed is separated from the program
code file map. Data files are now installed in the folder: C:\Documents and Settings\”username”\Local
Settings\Application Data\UniSABIII_1082.
8.7.2
SabSim Data simulator
Connecting the SabSim Data simulator to the UniSAB III panel
Start the SabSim Data simulator. Click on
File
and
New
. Click
OK
to the
New Module (Compressor Sim-
ulator)
and the simulator picture will open.
Click on
Connection/Configure
and insert the IP address of the UniSAB III panel you wish to connect to
and click
OK
(Port and node number should not be changed).