Engineering manual - UniSAB III 1.10.8
78/346
001930 en 2021.06
Compressor control and surveillance
Regulator type
Parameter
Minimum
Maximum
Factory
setting
Unit
Discharge
pressure
Sp 1
-1
-90
24
58
8
21.4
bar
°
C/R717
Sp 2
-1
-90
24
58
8
21.4
bar
°
C/R717
Sp 1
(SAB 193H-355H)
-1
-90
35.0
74.1
8
21.4
bar
°
C/R717
Sp 2
(SAB 193H-355H)
-1
-90
35.0
74.1
8
21.4
bar
°
C/R717
Sp 1
(SAB 157 HR)
-1
-90
52
90.0
8
21.4
bar
°
C/R717
Sp 2
(SAB 157 HR)
-1
-90
52
90.0
8
21.4
bar
°
C/R717
Nz
0.0
200
0.0
°
C/R717
Pb
0.1
999.9
10
°
C/R717
(T.Int.) Only
when PID=Yes
0.5
999.9
60.0
sec.
(T.Diff.) Only
when PID=Yes
0.0
99.9
0
sec.
Process out
temperature
(Hot water)
Sp 1
-60
100
20
°
C
Sp 2
-60
100
20
°
C
Nz
0.0
100
0
°
C
Pb
0.1
999.9
50
°
C
(T.Int.) Only
when PID=Yes
0.5
999.9
60.0
sec.
(T.Diff.) Only
when PID=Yes
0.0
99.9
0.0
sec.
Ext. cool
Sp 1
-999
999
0
Sp 2
-999
999
0
Nz
0
999.9
0
Pb
0
999.9
100
(T.Int.) Only
when PID=Yes
0.5
999.9
60
sec.
(T.Diff.) Only
when PID=Yes
0.0
99.9
0
sec.
Ext. heat
Sp 1
-999
999
0
Sp 2
-999
999
0
Nz
0
999.9
0
Pb
0
999.9
100
(T.Int.) Only
when PID=Yes
0.5
999.9
60
sec.
(T.Diff.) Only
when PID=Yes
0.0
99.9
0
sec.
Motor current
Sp 1
0
2500
2500
Amp
Limiter
Sp 2
0
2500
2500
Amp
Table 20: Settings - regulating parameters, screw compressors