Engineering manual - UniSAB III 1.10.8
001930 en 2021.06
65/346
Shutdown/alarm
Id
Danbuss
Profibus/
Modbus
Oil pump 2 error
shutdown
NA
82
Low oil separator temperature
alarm + shutdown
NA
83
High oil separator temperature
alarm
NA
84
Low oil circuit pressure
alarm
NA
85
Water pump error
shutdown
NA
85
High internal suction pressure
alarm + shutdown
NA
86
High pressure ratio
alarm + shutdown
NA
87
Liquid slugging
alarm
NA
88
VSD backspin
shutdown
NA
88
Network Connection to VSD
(VSD link missing)
alarm
NA
89
General drive error
shutdown
NA
89
Start up limiter active
alarm
NA
90
Feedback error from VSD
shutdown
NA
90
High separator flow
alarm
NA
91
Network Connection to VSD
(Drive link error)
shutdown
NA
91
Low main oil pressure
alarm
NA
92
Start up limiter error
shutdown
NA
92
Oil system error (oil level switch)
alarm
NA
93
No evaporator flow
shutdown
NA
93
No condenser flow
shutdown
NA
94
High process in temperature
alarm + shutdown
NA
95
Low process in temperature
alarm + shutdown
NA
96
Forced speed active
alarm
NA
97
Emergency stop
shutdown
NA
97
Low process out temperature
alarm + shutdown
NA
98
High process out temperature
alarm + shutdown
NA
99
High internal pressure
alarm + shutdown
NA
100
Start RPM limiter
alarm
NA
101
Start RPM limiter error
shutdown
NA
101
Low oil eco pressure
alarm + shutdown
NA
NA
Low Vi
alarm
NA
103
Critical oil circuit pressure
shutdown
NA
103
Lube pressure unload
alarm
NA
104
Oil pump low pressure
alarm + shutdown
NA
105
High balance pressure reduction
alarm + shutdown
NA
106
Low balance pressure reduction
alarm + shutdown
NA
107
VI slide position error
alarm
NA
108
Low discharge temperature difference
alarm
NA
109
Slide calibration error
alarm
NA
110
High Suction pressure gradient
alarm + shutdown
NA
111
1) May occur as alarm in MAN and AUTO.
2) Shutdown at prelubrication. Alarm during operation.
3) HPO/HPC only.
4) The shutdown
Low oil pump pressure during operation
applies to SAB 80. The shutdown is only activated at a discharge pres-
sure level below 16 bar.
5) Shutdown relay can be deactivated.
NA = Not available
Table 17: Shutdowns and alarms with identification numbers for screw compressors