Engineering manual - UniSAB III 1.10.8
206/346
001930 en 2021.06
UniSAB alarm
Max. pressure
increase 1 min.
[bar]
Flooded
evaporator
Min. suction superheat [K]
ensured by suction superheater
Suction
pressure
[
°°
C/R]
Suction
pressure
[bara]
< 1K
2K
3K
5K
-9
3.0
0.2
0.7
1.2
2.3
-8
3.2
0.2
0.7
1.3
2.4
-7
3.3
0.2
0.7
1.3
2.5
-6
3.4
0.2
0.8
1.3
2.5
-5
3.5
0.2
0.8
1.4
2.6
-4
3.7
0.2
0.8
1.4
2.7
-3
3.8
0.2
0.8
1.5
2.8
-2
4.0
0.2
0.9
1.5
2.8
-1
4.1
0.3
0.9
1.6
2.9
0
4.3
0.3
0.9
1.6
3.0
1
4.5
0.3
0.9
1.6
3.0
2
4.6
0.3
1.0
1.7
3.0
3
4.8
0.3
1.0
1.7
3.0
4
5.0
0.3
1.0
1.8
3.0
5
5.2
0.3
1.1
1.8
3.0
6
5.3
0.3
1.1
1.9
3.0
7
5.5
0.3
1.1
1.9
3.0
8
5.7
0.3
1.1
2.0
3.0
9
5.9
0.3
1.2
2.0
3.0
10
6.2
0.3
1.2
2.1
3.0
11
6.4
0.4
1.2
2.2
3.0
12
6.6
0.4
1.3
2.2
3.0
13
6.8
0.4
1.3
2.3
3.0
14
7.0
0.4
1.3
2.3
3.0
15
7.3
0.4
1.4
2.4
3.0
16
7.5
0.4
1.4
2.5
3.0
17
7.8
0.4
1.5
2.5
3.0
18
8.0
0.4
1.5
2.6
3.0
19
8.3
0.4
1.5
2.6
3.0
20
8.6
0.4
1.6
2.7
3.0
21
8.9
0.5
1.6
2.8
3.0
22
9.1
0.5
1.6
2.8
3.0
23
9.4
0.5
1.7
2.9
3.0
24
9.7
0.5
1.7
3.0
3.0
25
10.0
0.5
1.8
3.0
3.0
26
10.3
0.5
1.8
3.0
3.0
27
10.7
0.5
1.8
3.0
3.0
28
11.0
0.5
1.9
3.0
3.0
29
11.3
0.5
1.9
3.0
3.0
30
11.7
0.6
2.0
3.0
3.0
31
12.0
0.6
2.0
3.0
3.0
32
12.4
0.6
2.1
3.0
3.0
33
12.7
0.6
2.1
3.0
3.0
34
13.1
0.6
2.2
3.0
3.0
35
13.5
0.6
2.2
3.0
3.0
36
13.9
0.6
2.3
3.0
3.0
37
14.3
0.7
2.3
3.0
3.0
38
14.7
0.7
2.4
3.0
3.0
39
15.1
0.7
2.4
3.0
3.0
40
15.6
0.7
2.5
3.0
3.0
41
16.0
0.7
2.5
3.0
3.0
42
16.4
0.7
2.6
3.0
3.0
Summary of Contents for SABROE Unisab III Control