Engineering manual - UniSAB III 1.10.8
226/346
001930 en 2021.06
To manually enable the
Long Life
function for upgraded, older compressors in the SMC Mk 4 family, the
commissioning engineer must log into the
Superuser
level with the appropriate password, and set the
SMC LL
paramter to
Yes
.
Select
No
to deactivate the
Long Life
service intervals function.
6: Suction pressure gradient reset
0.0 to 20.0 *C [3.0 *C]
The
Suction pressure gradient reset
parameter defines a minimum suction superheat limit for compres-
sor start.
This parameter is only active when the
Suction pressure gradient limiter
function is enabled.
At start-up, UniSAB III will check if the
Suction superheat
is lower than the
Suction pressure gradient re-
set
parameter. If this is the case, the compressor will not start. A
Low suction superheat
alarm will be is-
sued and compressor state will be set to
Pause
.
See subsection
6.4.3 Compressor block 22: Suction press. grad
.
7: Yield rate up limitation
0.2 to 3.0 %/sec [2.0 %/sec]
The
Yield rate up limitation
parameter defines the max. yield change per second with which the regula-
tors can increase the compressor Yield [%].
See subsection
Yield decrease rate limiter
.
8: Yield rate down limitation
0.2 to 3.0 %/sec [1.0 %/sec]
The
Yield rate down limitation
parameter defines the max. yield change per second with which the regu-
lators can reduce the compressor Yield [%].
See subsection
Yield decrease rate limiter
.
6.4.8
External (User 1) input
See section