Engineering manual - UniSAB III 1.10.8
86/346
001930 en 2021.06
Compressor control and surveillance
changes to 0. The “old” starting number is stored and reinserted if UniSAB III is configured differently
from
capacity set point control
.
3.1.13
Climate compensation
This function can be used for both reciprocating and screw compressors without automatic Vi regulation.
The function is included in the picture
Setup/Compr.Control
and is further described in chapter
The inlet temperature set point on the water side of plants which are regulated by brine temperature or
hot water temperature can be controlled by the outside temperature. This requires a 4-20 mA tempera-
ture transducer, which is connected to the current inlet in UniSAB III as shown in the wiring diagrams in
the back of this manual.
Use a standard temperature transducer with a suitable temperature range, e.g. -30 - +25
°
C as shown in
Fig. 14. Note that the points of discontinuity in the diagram will be determined by the transducer measur-
ing range as seen in examples 1 and 2 below.
Fig. 14: Transducer measuring range
No further compensation will be made once the outside temperature is above the top point of discontinu-
ity and below the bottom point of discontinuity.
The factor by which the outside temperature should influence the inlet temperature positively or nega-
tively must be set in the
Brine
,
Hot water
or
User
regulator.
In the picture
Setup/Compr. Control
, select
Control on
=
Process out (brine)
or
Hot water
, or (with
User
regulator)
Ext. Cool/Ext. Heat
as well as
Climate compensation
= “Yes” in the picture
Setup/Compr.
Control
.
Example 1:
On a water cooling unit, the inlet temperature is to be corrected by the outside temperature.
•
If the outside temperature is +30
°
C or more, the inlet temperature should be +4
°
C.
•
If the outside temperature is +0
°
C or less, the inlet temperature should be +12
°
C.
In the menu
Setup/Compr. Control
, set
Control on
to
Process out
and
Climate compensation
on
Yes
. Se-
lect an outside sensor with a range of 0 - +30
°
C.
T
inlet
Sp 1 (-5°C)
Sp 2
(+25°C)
4 mA
(-30°C)
20 mA
(+25°)
T
out
Summary of Contents for SABROE Unisab III Control
Page 1: ...UniSAB III control Version 1 10 8 Engineering manual EN...
Page 2: ......
Page 347: ......