Communication extension card
CANopen communication card
-22-
COB-ID
Byte0
Byte1
0x000
0x01
0x00
3.4.4 Node protection (NMT Node Guarding)
By using the node protection service, the NMT master node can detect the current state of
each node.
Command
Request: Master station (remote frame) –> slave station
COB-ID
No data
0x700 + Node-ID
Response: Slave station -> master station
COB-ID
Byte0 (state value)
0x700 + Node-ID
Bit 7: Triggering bit; Bits 0 to 6: State
Description
The most significant bit (MSB) bit 7 of Byte0 (state value) in the response command is the
triggering bit, that is, the value of bit 7 is alternated between 0 and 1 each time when the slave
station transmits a response frame to distinguish frames. Bits 0 to 6 indicate the state of the
slave station. Table 3-5 describes the state values and their corresponding state.
Table 3-5 State values and their corresponding states
State value (Byte0: Bits 0–6)
State
0x00
Initializing
0x04
Stopped
0x05
Operation
0x7F
Pre-operational
Example
For example, the command for the master station to detect the state of slave station 3.
Master station (remote frame) -> slave station
COB-ID
No data
0x703
/
After receiving the node protection command transmitted by the master station, the slave
station transmits the following command response to the master station.
COB-ID
Byte0 (state value)
0x703
0x85
In the command, bit 7 of Byte0 is 1, and the state value is 0×05, indicating that slave station 3
is in the operation state. If receiving another node protection command, the slave station
transmits a command frame in which the state value is 0×05 to the master station, and the