Communication extension card
EtherNet/IP communication card
-68-
3
The task cannot be executed and one of the following error number is
returned:
1: Invalid command
2: Invalid data address
3: Invalid data value
4: Operation failure
5: Password error
6: Data frame error
7: Parameter read only
8: Parameter cannot be modified during VFD running
9: Password protection
5.4.4 Communication with the PLC
The following describes how the PLC (1769_L36ERMS) communicates with the EtherNet/IP
adapter module (using Studio 5000 as the configuration tool).
1.
Obtain the EDS file of the EtherNet/IP communication card.
The EDS file is used to specify device properties on the EtherNet/IP client. The client
uses the product code, device type, and main version to identify a device.
You can request the EDS file from your supplier or download the file
GD350_EthernetIP_V1.10.eds
from www.invt.com.
2.
Use Studio 5000 to add the EDS file to the PLC.
Open Studio 5000, right-click
TOOLS
, and choose
EDS Hardware Installation Tool
.