DC circuit breaker
Ingecon
®
μWind units (with or without transformers) may have an optional DC isolating switch.
There are several different models, although they all have the same electrical properties.
The advantage provided by this isolator is that it can isolate under load in case of emergency.
In any case, we recommend that other than in the case of an emergency, the unit be shut
down by means of the display before isolating.
DC circuit breaker
As long as the wind generator receives wind, the DC cables will carry potentially dangerous voltage
levels.
Never handle the connections before disconnecting the inverter from the grid and the wind generator.
Ingecon® μWind Interface (IWI) Connector
You may optionally request the inverter to be fitted with a
connector for connecting to the Ingecon
®
μWind Interface.
IWI connector
Transformer connectors
Ingecon
®
μWind units with transformer are supplied with the inverter and transformer in
separate boxes. They must be connected when installed using the cable supplied with the
transformer.
The connectors to link are as shown in the figure.
Connectors to be joined
5.3.2. Order of connecting the unit
The basic connections to be made with the inverter are as follows, in this order:
1.
Connecting auxiliary equipment (optional).
2.
Communication line (optional).
3.
Connecting the inverter and the transformer in units which include one.
4.
Connecting the inverter to the grid.
5.
Connecting the Ingecon
®
μWind Interface communications cable (optional).
6.
Connecting the DC cables from the wind generator or the Ingecon
®
μWind Interface (depending on the
configuration selected).
The following sections describe how to make these connections.
5.3.3. System wiring diagram
The layout will correspond to those in the figures in the majority of installations.
The regulations applicable to each installation and to each country in which the inverter is located must always be
observed.
AAY2000IKI04
30
Installation manual
Ingeteam Power Technology, S.A.
Summary of Contents for Ingecon mWind 2.5
Page 1: ...Ingecon Wind Installation manual...
Page 55: ...Notes...