electric shock complying with
EN 168-1994
for voltage testing tasks and opening or closing automatic switches under
load.
4.5. Inspection, control and handling tasks
The mandatory safety measures necessary in carrying out inspection, control and/or handling tasks on this unit are
defined below.
Opening method: The cover is opened and closed using a system requiring tools to remove it (nuts
and bolts).
It is strictly forbidden to gain access to the inside of the equipment through any other point than the
access cover provided for the purpose.
4.5.1. Inspection tasks
Access inside of the unit for inspection only via the front cover.
After completing the inspection, replace the front cover and secure it with the bolts supplied.
4.5.2. Control tasks
The only control task which can be carried out on this unit is the loading of software from the quick communications
connector located on the outside.
4.5.3. Handling tasks
All those tasks which are neither Inspection or Control will be considered to be Handling.
Before handling the equipment, ensure there is no voltage present. To achieve this, use the following protocol:
1.
Shut down the unit.
2.
Block the wind generator if a braking system is available.
3.
Disconnect the inverter DC input cable, isolate it, mark it and protect it.
4.
Disconnect the Vac cable.
5.
Wait 10 minutes for the internal capacitances to discharge, the hot parts to cool and the inverter’s fan blades
to stop turning.
6.
Open the door and discharge the Vbus by means of a suitable discharge resistance between the +VBUS and
-VBUS. Check there is no voltage
To carry out steps 2, 3, 4, 5 and 6, it will be necessary to use the PPE indicated in Section “4.4.3. Personal
Protection Equipment (PPE)” in this document for work with live parts.
Any work carried out which implies a modification of the original electrical settings must be proposed
to and accepted by Ingeteam.
AAY2000IKI04
24
Installation manual
Ingeteam Power Technology, S.A.
Summary of Contents for Ingecon mWind 2.5
Page 1: ...Ingecon Wind Installation manual...
Page 55: ...Notes...