The following screen will appear requesting confirmation or
cancellation of the modified value using the
or
respectively.
11:23
11/01/12
V/F ADJUSTMENTS
Fac
Cancel
11:23
11/01/12
V/F ADJUSTMENTS
Fac
Cancel
Changing the protection limits for voltage and frequency may result in failure to comply with the
standards to which the original unit was certified. In this case the certificates prior to the change will
be invalid.
Ingeteam accepts no liability for any type of problem caused by changing these limits.
8.5.5. Auxiliary relay
Ingecon
®
μWind units are fitted with an auxiliary relay which may be used for various functions.
Access the
AUXILIARY RELAY
submenu and press
to see
the various options.
11:23
11/01/12
Configuration
CountrY/rEguLationS
grid voLtagE
grounding
v/f adJuStMEntS
auXiLiarY rELaY
11:23
11/01/12
Configuration
CountrY/rEguLationS
grid voLtagE
grounding
v/f adJuStMEntS
auXiLiarY rELaY
The standard unit comes with the
Insulation fault
option selected.
The > symbol points to the option selected.
Use the
and
keys to select the desired configuration
and press
.
11:23
11/01/12
AUXILIARY RELAY
Insulation fault
Grid Connection
V/f Limits
Power Limit
11:23
11/01/12
AUXILIARY RELAY
Insulation fault
Grid Connection
V/f Limits
Power Limit
Insulation fault
Select
Insulation fault
if you wish the auxiliary relay to switch when the equipment detects a fault of this type.
11:23
11/01/12
AUXILIARY RELAY
Insulation fault
Grid Connection
V/f Limits
Power Limit
11:23
11/01/12
AUXILIARY RELAY
Insulation fault
Grid Connection
V/f Limits
Power Limit
11:23
11/01/12
AUXILIARY RELAY
InsULAtIon fAULt
Continue ?
Cancel
11:23
11/01/12
AUXILIARY RELAY
InsULAtIon fAULt
Continue ?
Cancel
AAY2000IKI04
46
Installation manual
Ingeteam Power Technology, S.A.