2.1.6. Acoustic contamination
When on, the inverter generates a slight buzzing sound.
Do not place it in an occupied room, or on light supports which might amplify this buzz. The mounting
surface must be firm and appropriate for the weight of the unit.
2.1.7. Ventilation
Ingecon
®
μWind TL
Ingecon
®
μWind
A zone of 30 cm above the unit and 20 cm below and at the sides must be left free of obstacles. Only
in this way will the unit’s cooling system operate correctly.
The cooling system designed for the unit varies from one unit to another as greater heating occurs at higher power
and this requires greater air flow to cool it. This is why some models are cooled by means of natural convection and
others use forced convection with one or two fans.
Natural convection
•
Ingecon
®
μWind 2.5
•
Ingecon
®
μWind 2.5 TL
•
Ingecon
®
μWind 3 TL
Forced convection (1 fan)
•
Ingecon
®
μWind 3.3
•
Ingecon
®
μWind 3.3 TL
•
Ingecon
®
μWind 3.68 TL
AAY2000IKI04
14
Installation manual