5. Installation
Before installing the Ingecon
®
μWind unit, the packaging must be removed, taking special care not to damage the
housing.
The inside of the box must be checked to ensure there is no moisture. If there are signs of moisture, the unit must not
be installed until it is completely dry.
All installation operations must obey the regulations in force.
Before starting the actions described under this point, it is important to identify each of the parts described in it and
to have gathered the necessary tools to carry them out.
5.1. General requirements for installation
•
The unit’s environment must be appropriate and meet the guidelines described in Chapter “2. System
description”. Additionally, the parts used in the rest of the installation must be compatible with the unit and
comply with the applicable legislation.
•
Ventilation and the space for work, which must be suitable for maintenance tasks according to the applicable
regulations in force.
•
The external connection devices, which must be suitable and sufficiently close as set forth in current
regulations.
•
The connecting cables must be of the appropriate section for the maximum current.
•
Special care must be taken to ensure that there are no external elements near the air inlets and outlets to
obstruct proper ventilation of the unit.
5.2. Fixing the unit to the wall
Ingecon
®
μWind units have a system for anchoring to the wall, using a fixing plate.
TL units
1.
Mark the attachment points for the plate on the wall. Use the template provided with the unit.
2.
Drill holes in the wall with a bit recommended for the screws to be used to secure the plate to the wall later.
3.
Fix the plate using wall plugs and stainless steel screws to prevent corrosion. Use fittings appropriate for the
weight of the unit.
AAY2000IKI04
25
Installation manual
Ingeteam Power Technology, S.A.