The guarantee does not cover damage caused by inadequate sealing of the unit.
Whenever the unit is opened, it is mandatory to lubricate the screws before closing it again to prevent them seizing.
6.2. Start-up
Once a general visual inspection, wiring check and sealing check has been carried out, proceed to connect power to
the unit while keeping it switched off.
The tasks outlined for this step must be carried out with the unit door always closed, thus avoiding possible contact
with live parts.
6.2.1. Configuration of the MPP curve
The Ingecon
®
μWind unit will impose the MPP working curve on the wind generator; this relates the DC input to the
power captured by the turbine, optimising its energy capturing conditions over a wide range of wind speeds.
0
1000
2000
3000
4000
5000
6000
100
200
300
400
500
Po
w
er (
W
)
Vdc
The curve may be configured with up to 15 characteristic points. The ranges of power and DC voltage values are as
follows:
Range of values
DC voltage
0
~
450 V
Power*
0
~
6100 W
* The output power will be limited by the unit’s rated power.
AAY2000IKI04
36