The parasitic capacitance between motor wires should not exceed 10 nF. If very long cables (> 100 meters) are used, this condition may not be met. In this case,
add series inductors between the Jupiter outputs and the cable. The inductors must be magnetically shielded, and must be rated for the motor surge current.
Typically the necessary values are around 100 μH.
Wire ferrules
It is recommended to use wire ferrules to prevent cable damage or wrong contacts. Ensure crimped ferrule diameter does not exceed 2.5 mm and the insulator is <
5 mm. Following are some suggested ferrules:
Manufacturer
Part number
Image
Description
WAGO
2.5 mm (14 AWG)
2
WAGO
1.5 mm (16 AWG)
2