INFICON
Description | 4
UL6000-Fab-Operating-instructions-iina75en1-04-(2109)
27 / 146
The actual measured leak rate is considered to be a background signal. Depending on
the selected variant of operation mode the background signal is hidden until the
display limit of the respective vacuum range is reached.
Display limits according to factory setting:
1×10
-1
mbar l/s in MASSIVE
1×10
-7
mbar l/s in GROSS
1×10
-10
mbar l/s in FINE
1×10
-12
mbar l/s in ULTRA
To switch off the function ZERO again, press the buttonZERO for about 2 seconds.
The function ZERO should be activated only if the leak rate signal is stable and no
leak is measured. See also "Set and use the function ZERO [
4.3.2.4 Meaning of the button LEDs
START button LED
STOP button LED
Meaning
Off
Flashing red
No connection to the control unit
Pulsing blue
Pulsing blue
Run-up
Off
Green
Standby vented (Vent valve open)
Off
Blue green
Standby pumped out (Vent valve
close)
Pulsing green
Off
Pump down
Off
Flashing green
Internal calibration
Flashing green
Off
External calibration
Green
Off
Measure
Yellow (warning, faulty
measurement possible)
Off
Measuring with warning not
acknowledged
Off
Red
Error
ZERO button LED
Off
No measurement operation
Off
ZERO blocked
Blue
ZERO off and HYDRO•S off
Green
ZERO ON
Yellow
ZERO off and HYDRO•S on
Summary of Contents for 550-520
Page 2: ...INFICON GmbH Bonner Strasse 498 50968 Cologne Germany ...
Page 119: ...INFICON Decommissioning 9 UL6000 Fab Operating instructions iina75en1 04 2109 119 146 ...
Page 140: ...11 Appendix INFICON 140 146 UL6000 Fab Operating instructions iina75en1 04 2109 11 3 RoHS ...
Page 144: ...Index INFICON 144 146 UL6000 Fab Operating instructions iina75en1 04 2109 ...
Page 145: ......
Page 146: ......