80
NOTE
Contacts of Reed relays may be clogged (reversibly) if connected to the device inputs without series
resistor.
►
Remedy:
Install a series resistor for the Reed relay:
Series resistor = max. input voltage / permissible current in the Reed relay
Example:
32 V / 500 mA = 64 Ohm
►
The series resistor must not exceed 5 % of the input resistance RE of the device input
data
sheet). Otherwise, the signal will not be detected as TRUE.
Example:
RE = 3 000 Ohm
max. series resistor = 150 Ohm