48
ifm
Programming Manual ecomatController/60-1 (CR711S) Operating System V2.5.0.n
2017-12-19
System description
Hardware description
>
Output type OUT Voltage-A
23126
The output provides 0...10 V e.g. for further controllers or actuators.
M3071n / CR071n: only
OUT3001
M3072n / CR072n:
OUT3001
and
OUT3002
The output is protected against overload and automatically switches off if overloaded.
13402
NOTICE
Reference voltage output can get damaged!
► Do NOT apply any external voltage!
Setting and measurement via FB Output or via system configuration:
>
Setting / measurement via system configuration
23424
Setting the reference voltage:
► Select [Local_IO] > [Outputs] > tab [Parameter] > [OUT3001 / OUT3002] in the device tree
► Enter the required value [V] in the column [Value]
permissible = 0...10
Monitoring of the values at the reference voltage output:
► Select [Local_IO] > [Outputs] > tab [IO-Mapping] > [OUT3001_I / OUT3002_I] in the device tree
>
[OutVoltageDiag] indicates the measured voltage in [mV]
>
Setting /measurement via FB Output
23425
Setting the reference voltage:
► Use the inputs in the FB output as follows:
[uiChannel] = 3001 / 3002
[uiValue] = required voltage in [mV]
permissible = 0...10000
Monitoring of the values at the reference voltage output:
► Read the outputs in the FB output as follows:
>
[uiOutVoltage] indicates the measured voltage in [mV]
[uiOutCurrent] indicates the measured current in [mA]
Details
→ FB
Output
(