Programming Manual ecomatController/60-1 (CR711S) Operating System V2.5.0.n
2017-12-19
ifm function libraries
Library ifmIOcommon.library
>
Output parameters
23163
Parameters
Data type
Description
Possible values
xError
BOOL
Indication if an error occurred during the FB
execution
FALSE
No error occurred or the FB is
still being executed
TRUE
Error occurred
Action could not be
executed
Note diagnostic
information
eDiagInfo
DIAG_INFO Diagnostic information
→ List below (diagnostic codes:)
xPrepared
BOOL
State of the FB outputs
FALSE
FB outputs still invalid; FB is
still processed
TRUE
FB outputs valid; FB has been
processed
xOutState
BOOL
Return value activation state of the selected
output
The state may deviate from the required
output state if e.g. a safety function has
deactivated an output group due to an error.
FALSE
Output is deactivated
TRUE
Output is activated
uiOutVoltage
UINT
Current output voltage in [mV]
Only available for the operating modes
"analogue" and "sensor"
0
Operating mode neither
"analogue" nor "sensor"
0
Operating mode "analogue" or
"sensor"
uiOutCurrent
UINT
Present output current in [mA]
Not available for the operating types
OUT_DIGITAL_CSI and
OUT_ANALOGUE_10
available = 0...final value of the
measuring range
>