2: P
RODUCT
S
PECIFICATIONS
2-70
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
■
Analog Output Specifications
*1 The arbitrary setting is a function that uses the digital resolution data by scaling it to arbitrary data (that arbitrarily sets the lower limit value and
the upper limit value). The range setting (-32,768 to 32,767) is specified with data registers.
Output Internal Circuit
Output Type and Output Range
Voltage
Current
0 to 10 V
-10 to 10 V
4 to 20 mA
0 to 20 mA
Load
Impedance
1 k
Ω
or higher
300
Ω
or lower
Load Type
Resistive load
DA
Conversion
DA Conversion Time
1 ms
Output Update Interval
1 ms
Total Output System Transfer Time
DA conversion time + Output Update In 1 scan time
Output Error
Maximum Error
at 25°C
FC6A-L03CN1
±0.1% of full scale
FC6A-L06A1
±0.2% of full scale
FC6A-K4A1
Temperature
Coefficient
FC6A-L03CN1
0.006%/°C
FC6A-L06A1
0.01%/°C
FC6A-K4A1
Output Ripple
1 LSB or lower
Overshoot
0%
Data
Digital Resolution
4,096 steps (12 bits)
Input Value per Step
2.44 mV (0 to 10 V)
4.88 mV (-10 to +10 V)
4.88
μ
A (0 to 20 mA)
3.91
μ
A (4 to 20 mA)
Application
Can be arbitrarily set for each CH in a range between -32,768 to 32,767
Monotonicity
Yes
Current Loop Open
Not detectable
Noise
Resistance
*3
Maximum Temporary Deviation
during Electrical Noise Tests
±4% or less of full scale
Recommended Cable for Noise
Immunity
Current/voltage:
P
air shielded cable
Other:
P
air cable
Crosstalk
1 LSB
Isolation
Between Output and Power Circuit
Transformer isolated
Between Output and Internal Circuit
Photocoupler isolated
Effect of Improper Output Connection
No damage
Selection of Analog Output Signal Type
Using programming software
Calibration or Verification to Maintain Rated Accuracy
Not possible
Analog Signal
Switching Signal
Analog Output
Element
+
–
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...