FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
3-37
3: I
NSTALLATION
AND
W
IRING
■
HMI Module and Cartridge
Crimping Tool
The following crimping tool can be used with FC6A Series MicroSmart.
Module Type
HMI Module
Cartridges
Wire Type
UL1007
UL2464
UL1015
UL1007
UL2464
UL1015
Stripping length (mm)
7
5
Wire thickness (mm
2
)
0.14 to 2.5
0.14 to 1.50
Wire
gauge
AWG 24
1-wire
usage
AI 0,25- 6 (3203040)
Yes
―
Yes
―
AI 0,25- 8 (3203037)
Yes
―
―
―
AI 0,25-10 (3241128)
―
―
―
―
AWG22
1-wire
usage
AI 0,34- 6 (3203053)
Yes
―
Yes
―
AI 0,34- 8 (3203066)
Yes
―
―
―
AI 0,34-10 (3241129)
―
―
―
―
AWG20
1-wire
usage
AI 0,5- 6 (3200687)
Yes
―
Yes
―
AI 0,5- 8 (3200014)
Yes
―
―
―
AI 0,5- 8 GB (1208966)
―
Yes
―
―
AI 0,5-10 (3201275)
―
―
―
―
AI 0,5-10 GB (3203150)
―
―
―
―
2-wire
usage
AI-TWIN 2 x 0,5-8
(3200933)
Yes
―
―
―
AI-TWIN 2 x 0,5-10
(3203309)
―
―
―
―
AWG18
1-wire
usage
AI 0,75- 6 (3200690)
Yes
―
―
―
AI 0,75- 8 (3200519)
Yes
―
―
―
AI 0,75-10 (3201288)
―
―
―
―
AI 1-8 (3200030)
―
Yes
―
―
AI 1-10 (3200182)
―
―
―
―
2-wire
usage
AI-TWIN 2 x 0,75-8
(3200807)
Yes
―
―
―
AI-TWIN 2 x 0,75-10
(3200975)
―
―
―
―
AWG16
1-wire
usage
AI 1,5- 6 (3200755)
Yes
Yes
―
―
AI 1,5- 8 (3200043)
Yes
Yes
―
―
AI 1,5-10 (3200195)
―
―
―
―
2-wire
usage
AI-TWIN 2 x 1,5-8
(3200823)
―
―
―
―
Screwdriver
SZS 0.4×2.5 (1205037)
―
Yes
SZS 0.6×3.5 (1205053)
Yes
―
Tightening torque (N)
0.5 to 0.6
0.22 to 0.25
Tool Name
Phoenix Contact Model Number (order number)
Crimping tool
CRIMPFOX 6 (1212034)
•
Do not touch live terminals. There is a risk of electric shock.
•
When powered, the terminals that are connected to external devices may become hot. Do not touch the terminals
immediately after turning the power off.
•
Do not touch the power supply terminals immediately after turning the power off. There is a risk of electric shock.
•
Insert the wire all the way to the tip of the ferrule and crimp it.
•
When connecting stranded wire or multiple wires to a terminal block, use a ferrule. Otherwise there is a risk of wires
becoming disconnected.
•
When using single wires, you do not need to use ferrules.
•
Single wire assumes the use of one wire. Do not attach two or more wires to the one connector hole.
Caution
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...