5: F
UNCTIONS
AND
S
ETTINGS
5-48
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
32-bit Data Storage Setting
This section describes the methods of storing 32-bit data in data registers.
Function Specification
When the double-word, long, or float data type is selected for the source or destination device, the data is loaded from or stored
to two consecutive data registers. The order of the two devices can be selected from the following two settings in the
Function
Area Settings
.
Devices
When the devices listed below are used as a double-word device, two consecutive devices are processed according to the 32-bit
data storage settings.
Setting
Description
From Upper Word (Default)
When a data register, timer, or counter is used as a double-word device, the high-word data is loaded from
or stored to the first device selected. The low-word data is loaded from or stored to the subsequent
device.
This is identical with the 32-bit data storage of OpenNet Controller and FC4A/FC5A MicroSmart.
From Lower Word
When a data register, timer, or counter is used as a double-word device, the low-word data is loaded from
or stored to the first device selected. The high-word data is loaded from or stored to the subsequent
device.
Device
Device Address
Data Register
D0 - D7999, D10000 - D55999
Special Data Register
D8000 - D8499
Timer
T0 - T1023
Counter
C0 - C511
Data: The following data composed of 32 bits is subject to this setting.
•
Device values of advanced instructions with the data processing units D (double word), L (long), F (float)
•
Pulse output preset values and current values
•
High-speed counter function current values, preset values, and reset values
•
Frequency measurement values in frequency measurement
•
Double word counter instruction preset values
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...