Supplementary Descriptions of the Special Data Registers
■
D8000: Quantity of Inputs
The number of FC6A Series MicroSmart inputs is written to this register.
The total number of inputs for the CPU module and the expansion modules is written to this register.
■
D8001: Quantity of Outputs
The number of FC6A Series MicroSmart outputs is written to this register.
The total number of outputs for the CPU module and the expansion modules is written to this register.
■
D8002: CPU Module Type Information
CPU module type information is written this register.
0 (00h): 16-I/O type
1 (01h): 24-I/O type
2 (02h): 40-I/O type (All-in-One Type)
18 (12h): 40-I/O type (CAN J1939 All-in-One Type)
■
D8005: General Error Code
FC6A Series MicroSmart general error information is written to this register. When a general error occurs, the bit corresponding
to the error occurred turns on. The general error and user program execution error can be cleared by writing "1" to the most
significant bit of D8005. For details on general error codes, see "General Error Codes" on page 13-3.
■
D8006: User Program Execution Error Code
FC6A Series MicroSmartuser program execution error information is written to this register. When a user program execution
error occurs, the error code corresponding to the error that occurred is written to this register. For details on user program
execution errors, see "User Program Execution Error" on page 13-6.
■
D8008 to D8021: Calendar/Clock Data
D8008 through D8021 are used for reading calendar/clock data from the internal clock and for writing calendar/clock data to the
internal clock. For details on the calendar/clock data, see "Clock Function" on page 5-55.
■
D8022 to D8025: Scan Time Data
D8022 through D8025 are special data registers for checking the scan time and configuring the constant scan time. For details
on the scan time, see "Constant Scan Time" on page 5-53.
■
D8026: Communication Mode Information (Port 1 to 3)
This register indicates communication mode information for Port 1 to Port 3.
The allocation of communication ports in the device (bit assignment) is as follows.
D8492
Expansion Module Slot 12
Information
Type ID/Status
―
R
D8493
System Software Version
―
R
D8494
Expansion Module Slot 13
Information
Type ID/Status
―
R
D8495
System Software Version
―
R
D8496
Expansion Module Slot 14
Information
Type ID/Status
―
R
D8497
System Software Version
―
R
D8498
Expansion Module Slot 15
Information
Type ID/Status
―
R
D8499
System Software Version
―
R
Device
Address
Description
Update Timing
R/W
Bit
15
Bit
0
Bit
7
Bit
8
Bit
4
Port 1
Port 2
Port 3
Bit
3
Bit
11
0 (0000): Maintenance communication
1 (0001): User communication
2 (0010): Modbus RTU master
3 (0011): Modbus RTU slave
4 (0100): Data link communication
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...