Forced I/O function
Inputs can be forced on/off regardless of the status of physical inputs, and outputs can be forced on/off regardless of the ladder
logic using the forced I/O function in WindLDR. The force input function can be used to monitor or online edit mode to test the
ladder logic without the need of wiring the input terminals or turning on the actual inputs. The force output function can be used
to turn on/off the outputs to the external devices.
Devices
All the inputs and outputs of the FC6A Series MicroSmart can be forced on/off individually.
Forced I/O Status
Events of the FC6A Series MicroSmart and effects on the forced I/O settings are shown below.
Note:
Force function has no effect on high-speed counters, catch inputs, or interrupt inputs. The stop or reset input can be initiated using the force
function, but the force settings will be cleared as soon as the reset input is turned on.
Checking the Forced I/O Function Execution State
The forced I/O function status (running or stopped) can be checked in WindLDR, the FC6A Series MicroSmart error indicator LED
[ERR], or the RUN screen or STOP screen on the HMI module's LCD.
The forced I/O function execution status while stopped cannot be checked with the FC6A Series MicroSmart power indicator LED
[PWR] and the operation indicator LED [RUN]. For the power indicator LED [PWR] and the operation indicator LED [RUN], see
"CPU Module" on page 2-2.
The forced I/O may cause unexpected operation of the FC6A Series MicroSmart. Make sure of safety before forcing inputs or
outputs.
Caution
Type
Device Range
Inputs
Outputs
16-I/O type
I0 to I10, I30 to I627
Q0 to Q6, Q30 to Q627
24-I/O type
I0 to I15, I30 to I627
Q0 to Q11, Q30 to Q627
40-I/O type
I0 to I27, I30 to I627
Q0 to Q617, Q30 to Q627
Events
Forced I/O Status
When the FC6A Series MicroSmart starts running
The force settings are retained. The forced inputs and outputs are kept on/off
even after the FC6A Series MicroSmart is stopped, regardless of the status of
M8025 (maintain outputs while FC6A Series MicroSmart is stopped).
When the FC6A Series MicroSmart is stopped.
When the FC6A Series MicroSmart is powered up
The force settings are retained, but the force is suspended. If the battery is
dead, the force settings are cleared.
When user program download is executed
The force settings are retained, and whether the force will be suspended or
not can be selected in the Download Program dialog box.
When Reset Input is turned on
The force settings are cleared.
When Clear All Devices is executed in the PLC Status dialog
box of WindLDR
When the system software download is executed
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...