Frequency Measurement
This section describes frequency measurement, which measures the frequency of pulses input to an external input. Frequency
measurement is a function that measures the frequency of pulses input to an external input.
These input pulses are processed with dedicated hardware device in FC6A Series MicroSmart, so frequencies can be measured
with no relation to the scan time. The measurement results are stored in special data registers and they are updated with each
scan.
Function Specification
The FC6A Series MicroSmart external inputs are used by switching between normal input, high-speed counters, catch input,
interrupt input, and frequency measurement. To use frequency measurement, specify the relevant group as
Frequency
Measurement
in the WindLDR
Function Area Settings
.
Frequency measurement can be used with the following external inputs.
*1 Can be used as a normal input.
The frequency measurement results are stored in the following special data registers by external input group. The gate inputs can
also be controlled by special internal relays, so frequency measurements can be started and stopped by turning the gate inputs on
and off.
Notes:
•
R/W is the abbreviation for read/write. When R/W, it can be read and written. When R, it can only be read. When W, it can only be written.
•
To reflect the measurement results in the special data registers, a maximum of calculation cycle + scan time is required. However, when the
FRQRF instruction is used during ladder processing, the frequency value of the special data registers can be updated to the latest value. The
latest calculation result can be read within 250 ms regardless of the input frequency.
•
The data registers for the upper word and the lower word of the measurement value change according to the 32-bit data storage method
specified. For details, see "32-bit Data Storage Setting" on page 5-48.
Group
1
2
3
4
5
6
External Input
I2
I0
I1
I3
I4
I5
I6
I7
Frequency
Measurement Value
Yes
Yes
Yes
Yes
—
Yes
Yes
Frequency
Measurement Range
4 Hz to 100 kHz
4 Hz to 5 kHz
4 Hz to 100 kHz
Measurement Error
Less than ±10% (4 Hz or higher and less than 4 kHz), less than ±0.1% (4 kHz or higher)
Calculation Cycle
Within 1 s (less than 4 kHz), within 250 ms (4 kHz or higher)
Group
1
2
3
4
5
6
Read/Write
Gate Input
D8031
D8052
D8035
D8041
D8045
D8060
R/W
Frequency
Measurement
Value (32 bits)
Upper Word
D8210
D8192
D8218
D8222
D8226
D8198
R
Lower Word
D8211
D8193
D8219
D8223
D8227
D8199
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...