5: F
UNCTIONS
AND
S
ETTINGS
5-12
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
Internal Relay ‘Keep’ Designation (M0000 to M7997)
Internal Relay ‘Keep’ Designation (M10000 to M17497)
Shift Register ‘Keep’ Designation
Counter ‘Clear’ Designation
Data Register ‘Clear’ Designation (D0000 to D7999)
Data Register ‘Clear’ Designation (D10000 to D55999)
Notes:
•
When the FC6A Series MicroSmart has lost its keep data, the
Run/Stop Selection at Memory Backup Error
setting has priority over the
Run/Stop Selection at Power Up
setting.
•
Relays and registers specified as
Clear Al
l or
Clear Specified Range
are cleared when the FC6A Series MicroSmart starts operation. The
values while the power is off are retained until the power is turned on and operation is started.
•
Keep/clear settings cannot be configured for special data registers. They operate the same as
Clear All
.
•
Keep/clear settings cannot be configured for special internal relays. For operation when the power is shut off and when stopped, see
"Devices" - "Special Internal Relay" on page 6-3.
Clear All:
Clears the internal relays (M0000 to M7997) when the FC6A Series MicroSmart starts operation.
Keep All:
Keeps the status of the internal relays (M0000 to M7997) while the FC6A Series MicroSmart power is off.
Keep Specified Range:
Keeps the status of the internal relays in the specified range while the FC6A Series MicroSmart power is off.
When a range of M50 through M100 is designated as shown in the example above, M50 through M100 are keep
types, M0 through M47 and M101 through M7997 are clear types.
Clear All:
Clears the internal relays (M10000 to M17497) when the FC6A Series MicroSmart starts operation.
Keep All:
Keeps the status of the internal relays (M10000 to M17497) while the FC6A Series MicroSmart power is off.
Keep Specified Range:
Keeps the status of the internal relays in the specified range while the FC6A Series MicroSmart power is off.
Clear All:
All shift register bit statuses are cleared at startup (default).
Keep All:
All shift register bit statuses are maintained at startup.
Keep Specified Range:
A specified range of shift register bits are maintained at startup. Enter the start “keep” number in the left field
and the end “keep” number in the right field. The start “keep” number must be smaller than or equal to the end
“keep” number.
Clear All:
All counter current values are cleared at startup.
Keep All:
Keeps all counter current values while the FC6A Series MicroSmart power is off.
Clear Specified Range:
A specified range of counter current values are cleared at startup. Enter the start “clear” number in the left field
and the end “clear” number in the right field. The start “clear” number must be smaller than or equal to the end
“clear” number.
Clear All:
Clears the values of the data registers (D0000 to D7999) when the FC6A Series MicroSmart starts operation.
Keep All:
Keeps the values of the data registers (D0000 to D7999) while the FC6A Series MicroSmart power is off.
Clear Specified Range:
A specified range of data register values are cleared at startup. Enter the start “clear” number in the left field and
the end “clear” number in the right field. The start “clear” number must be smaller than or equal to the end
“clear” number.
Clear All:
Clears the values of the data registers (D10000 to D55999) when the FC6A Series MicroSmart starts operation.
Keep All:
Keeps the values of the data registers (D10000 to D55999) while the FC6A Series MicroSmart power is off.
Clear Specified Range:
A specified range of data register values are cleared at startup. Enter the start “clear” number in the left field and
the end “clear” number in the right field. The start “clear” number must be smaller than or equal to the end
“clear” number.
End Keep Number (
≥
Start Keep Number)
Start Keep Number
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...