(5) Sample Time
Analog values are converted to digital values at the interval of the sampling duration time. Depending on the analog module,
you may be able to change the sample duration time setting.
(6) Thermistor settings
When NTC thermistor is selected for the FC6A-J8CU1 signal type, the following parameters must be set.
(7) Data
Data refers to the input analog values converted to digital values at the interval of the sampling duration time.
The data is written to data registers in the END processing of each scan. The analog input data is updated regardless of whether
the FC6A Series MicroSmart is stopped or running. The data is not guaranteed when the status (8) is a value other than "0".
Type
Signal Type
Sample Time
FC6A-J2C1
0 to 10 V
1 ms
-10 to +10 V
1 ms
0 to 20 mA
1 ms
4 to 20 mA
1 ms
FC6A-J4A1
0 to 10 V
1 ms/10 ms
-10 to +10 V
1 ms/10 ms
0 to 20 mA
1 ms/10 ms
4 to 20 mA
1 ms/10 ms
FC6A-J8A1
0 to 10 V
1 ms/10 ms
-10 to +10 V
1 ms/10 ms
0 to 20 mA
1 ms/10 ms
4 to 20 mA
1 ms/10 ms
Expansion 0 to 20 mA
1 ms/10 ms
Expansion 4 to 20 mA
1 ms/10 ms
FC6A-J4CN1
0 to 10 V
100 ms/10 ms
-10 to +10 V
100 ms/10 ms
0 to 20 mA
100 ms/10 ms
4 to 20 mA
100 ms/10 ms
Thermocouple
104 ms
Resistance thermometer
104 ms
FC6A-J8CU1
Thermocouple
104 ms
NTC/PTC thermistor
104 ms
PTC thermistor (threshold)
104 ms
Resistance measurement
104 ms
FC6A-L06A1
0 to 10 V
1 ms/10 ms
-10 to +10 V
1 ms/10 ms
0 to 20 mA
1 ms/10 ms
4 to 20 mA
1 ms/10 ms
FC6A-L03CN1
0 to 10 V
100 ms/10 ms
-10 to +10 V
100 ms/10 ms
0 to 20 mA
100 ms/10 ms
4 to 20 mA
100 ms/10 ms
Thermocouple
104 ms
Resistance thermometer
104 ms
Parameter
Description
Range
R0
The thermistor resistance in "T0"°C
0 to 65,535
T0
Temperature
-32,768 to 32,767
B
Thermistor B constant
-32,768 to 32,767
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...