Mounting Direction
Mount the MicroSmart modules horizontally on a vertical plane as shown on the preceding page. Keep a sufficient spac-
ing around the MicroSmart modules to ensure proper ventilation and keep the ambient temperature between 0°C and
55°C.
All-in-One Type CPU Module
When the ambient temperature is 35°C or below, the all-in-one type CPU modules can also be mounted upright on a hor-
izontal plane as shown at left below. When the ambient temperature is 40°C or below, the all-in-one type CPU modules
can also be mounted sideways on a vertical plane as shown in the middle below.
Allowable Mounting Direction at
35°C or below
Incorrect Mounting Direction
Allowable Mounting Direction at
40°C or below
Slim Type CPU Module
Always mount the slim type CPU modules horizontally on a vertical plane as shown on the preceding page. Any other
mounting directions are not allowed.
Incorrect Mounting Direction
Incorrect Mounting Direction
Incorrect Mounting Direction