MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
Programming WindLDR
WindLDR ver. 5.0 or later has the ANST (Set Analog Module Parameters) macro for easy programming of analog I/O mod-
ules.
1.
Place the cursor where you want to insert the ANST instruction on the ladder editing screen, type
ANST
and press the Enter
key.
The Set Analog Module Parameters dialog box appears.
2.
Select the slots where analog I/O modules are mounted.
All slots are selected to use seven analog I/O modules as default. Click the check box to deselect slots where analog I/O
modules are
not
mounted.
When using analog I/O modules on Slots 1, 3, 6, and 7, deselect Slots 2, 4, and 5 as shown below.