9: A
NALOG
I/O C
ONTROL
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
9-7
12.
View the data register numbers allocated to Data and Status.
Parameter
DR Allocation
Data
Analog I/O Data
Stores the digital data converted from an analog input sig-
nal or converted into an analog output signal.
Designated as source device S4 (process variable) of the
PID instruction.
END Refresh Type
Data registers are automatically allocated depending on
the slot where the analog I/O module is mounted.
Ladder Refresh Type
Data registers are automatically allocated depending on
the number designated in the DR Device Address field.
Status
Analog I/O Operating Status
Stores an analog I/O operating status code.
See pages 9-14 and 9-17.
13.
Click the
OK
button to save changes and exit the Configure Parameter dialog box.
14.
Repeat the same steps for other slots.
15.
When finished, click the
OK
button to save changes and exit the Set Analog Module Parameters dialog box.