5: S
PECIAL
F
UNCTIONS
5-12
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
Programming WindLDR (All-in-One Type CPU Modules)
1.
From the WindLDR menu bar, select
Configuration
>
Input Configuration
.
The Function Area Settings dialog box for Input Configuration appears.
2.
When using high-speed counter HSC1, select
Two/Single-phase High-
speed Counter
in the Group 1 pull-down list box.
When using high-speed counters HSC2 through HSC4, select
Single-phase
High-speed Counter
in the Groups 2 through 4 pull-down list boxes.
The High-speed Counter Settings dialog box appears.
CPU Module
Comparison Output
FC5A-C10R2/C/D
Q0 to Q3
FC5A-C16R2/C/D
Q0 to Q6
FC5A-C24R2/C/D
Q0 to Q7, Q10 to Q11
Mode
Select
Two-phase High-speed Counter
or
Single-phase High-speed Counter
for HSC1. Only Single-phase High-speed Counter is available for HSC2
through HSC4.
Enable Comparison
Click the check box to enable the high-speed counter comparison output, and specify an output number available on the
CPU module in the
Comparison Output
field. When the preset value is reached (single-phase high-speed counter) or
when current value overflow or underflow occurs (two-phase high-speed counter), the specified comparison output is
turned on and remains on until a comparison output reset special internal relay (M8030, M8034, M8040, or M8044) is
turned on.
Use HSC Reset Input
Click the check box to enable high-speed counter reset input I2 for HSC1 only. When input I2 is turned on, the current
value in D8045 is reset depending on the high-speed counter mode.
Single-phase
The current value is reset to 0. The value stored in D8046 (high-speed counter preset value) at this point takes
effect for the subsequent counting cycle.
Two-phase
The current value is reset to the value stored in D8046 (high-speed counter reset value). The two-phase high-
speed counter counts subsequent input pulses starting at the reset value.
Since these settings relate to the user program, the user program must be downloaded to the MicroSmart after changing
any of these settings.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]