2: M
ODULE
S
PECIFICATIONS
2-28
FC5A MicroSmart User’s Manual FC9Y-B1268
General Specifications
Normal Operating Conditions
CPU Module
FC5A-D12K1E
FC5A-D12S1E
Operating Temperature
0 to 55°C (operating ambient temperature)
Storage Temperature
–25 to +70°C
Relative Humidity
10 to 95% (non-condensing, operating and storage humidity)
Pollution Degree
2 (IEC 60664-1)
Degree of Protection
IP20 (IEC 60529)
Corrosion Immunity
Atmosphere free from corrosive gases
Altitude
Operation: 0 to 2,000m (0 to 6,565 feet)
Transport:
0 to 3,000m (0 to 9,840 feet)
Vibration Resistance
When mounted on a DIN rail or panel surface:
5 to 8.4 Hz amplitude 3.5 mm, 8.4 to 150 Hz acceleration 9.8 m/s
2
(1G)
2 hours per axis on each of three mutually perpendicular axes (IEC 61131-2)
Shock Resistance
147 m/s
2
(15G), 11 ms duration, 3 shocks per axis on three mutually perpendicular axes
(IEC 61131-2)
ESD Immunity
Contact discharge: ±4 kV, Air discharge: ±8 kV (IEC 61000-4-2)
Weight
200g
Power Supply
Rated Power Voltage
24V DC
Allowable Voltage Range
20.4 to 26.4V DC (including ripple)
Maximum Input Current
700 mA (26.4V DC)
Maximum Power Consumption
(Note 1, 2)
CPU 7 I/O m expansion 8 I/O modules
19W (26.4V DC)
Allowable Momentary Power
Interruption
10 ms (at 24V DC)
Dielectric Strength
Between power and
terminals:
500V AC, 1 minute
Between I/O and
terminals:
500V AC, 1 minute
Insulation Resistance
Between power and
terminals:
10 M
minimum (500V DC megger)
Between I/O and
terminals:
10 M
minimum (500V DC megger)
Noise Resistance
DC power terminals:
1.0 kV, 50 ns to 1 µs
I/O terminals (coupling clamp):
1.5 kV, 50 ns to 1 µs
Inrush Current
50A maximum (24V DC)
Grounding Wire
UL1015 AWG22, UL1007 AWG18
Power Supply Wire
UL1015 AWG22, UL1007 AWG18
Effect of Improper Power Supply
Connection
Reverse polarity:
No operation, no damage
Improper voltage or frequency:
Permanent damage may be caused
Improper lead connection:
Permanent damage may be caused
Note 1:
Among relay output modules connected to the CPU module, a maximum of 54 points can be turned on simultaneously. Among
relay outputs connected beyond the expansion module, a maximum of 54 points can be turned on simultaneously. Relay outputs
exceeding these limits may not turn on correctly.
Note 2:
Maximum power consumption for individual CPU module is 3.0W (125 mA at 24V DC).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]