Programming WindLDR
When using the user communication function to communicate with an external RS232C or RS485 device, set the commu-
nication parameters for the MicroSmart to match those of the external device.
Note:
Since communication parameters in the Function Area Settings relate to the user program, the user program must be down-
loaded to the MicroSmart CPU module after changing any of these settings.
1.
From the WindLDR menu bar, select
Configuration
>
Communication Ports
.
The Function Area Settings dialog box for Communication Ports appears.
2.
In the Communication Mode pull-down list for Port 1 through Port 7, select
User Protocol
. (Click the
Configure
button when
changing previous settings.)
The User Protocol dialog box appears.
When
2550 ms
is selected in the Receive Timeout box, the receive timeout function is disabled.
3.
Select communication parameters to the same values for the device to communicate with.
4.
Click the
OK
button.