Analog Input Error Settings:
Analog Output Operation Mode: 4 to 20 mA
Maximum value tolerance: 2%
Minimum value tolerance: 1%
20.32
20
4
3.84
Upper tolerance
Full Scale (16 mA)
Lower tolerance
Analog Output Parameters
Analog output parameters include the analog output signal type, analog output data type, analog output minimum and
maximum values, analog output data, and analog output operating status. This section describes these parameters in
detail.
Analog Output Signal Type
A total of three analog output signal types are available, depending on the analog I/O or analog output module. Select an
analog output signal type for each analog output channel. When a channel is not used, select the default value or
Not
used
for the channel.
Parameter
FC4A-L03A1
FC4A-L03AP1
FC4A-K1A1
FC4A-K2C1
FC4A-K4A1
0
Voltage output
0 to 10V DC
–10 to +10V DC
0 to 10V DC
1
Current output
4 to 20 mA DC
255
Not used
—
—
—
X
X
Analog Output Data Type
A total of two analog output data types are available, depending on the analog I/O or analog output module. Select an
analog output data type for each analog output channel.
Parameter
FC4A-L03A1
FC4A-L03AP1
FC4A-K1A1
FC4A-K2C1
FC4A-K4A1
0
Binary data
Voltage
0 to 4095
–25000 to 25000
0 to 4095
Current
0 to 50000
1
Optional range
Voltage
Analog output data minimum value to maximum value (–32768 to 32767)
Current
Analog Output Minimum/Maximum Values
For analog output values, when Optional range is selected for the Data Type, designate the analog output data minimum
and maximum values which can be –32,768 through 32,767.