To suspend the forced I/O, click the Start/Suspend Force button
.
Even though I0 is designated,
forced I/O is suspended and
actual input status is read to the
CPU module.
The forced inputs or outputs remain designated until the forced I/O designation is released.
6.
To release the forced I/O designation, click the Force Release button
.
Input I0 is released from the
forced I/O designation. Even
when forced I/O is enabled,
actual input status is read to the
CPU module.
Now input I0 works as a normal input.
Note:
Make sure that all the forced inputs and outputs are released when the test using the forced I/O function is finished. Select
Delete All
from the right click menu in the Forced I/O List dialog box to release all the forced inputs and outputs at once.