11: D
ATA
L
INK
C
OMMUNICATION
11-6
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
Data Link Communication between Master and Slave Stations
The master station has 6 data registers assigned to transmit data to a slave station and 6 data registers assigned to
receive data from a slave station. The quantity of data registers for data link can be selected from 0 through 6 using
WindLDR. The following examples illustrate how data is exchanged between the master and slave stations when 2 or 6
data registers are used for data link communication with each of 31 slave stations.
Example 1: Transmit Data 2 Words and Receive Data 2 Words
Master Station
D8069
Communication Error
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8070
Communication Error
D912 - D913
Transmit Data
D918 - D919
Receive Data
D8071
Communication Error
D924 - D925
Transmit Data
D930 - D931
Receive Data
D8072
Communication Error
D936 - D937
Transmit Data
D942 - D943
Receive Data
D8098
Communication Error
D1248 - D1249
Transmit Data
D1254 - D1255
Receive Data
D8099
Communication Error
D1260 - D1261
Transmit Data
D1266 - D1267
Receive Data
Slave Stations
D8069
Communication Error
Slave Station 1
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 2
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 3
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 4
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 30
D900 - D901
Transmit Data
D906 - D907
Receive Data
D8069
Communication Error
Slave Station 31
D900 - D901
Transmit Data
D906 - D907
Receive Data
Example 2: Transmit Data 6 Words and Receive Data 6 Words
Master Station
D8069
Communication Error
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8070
Communication Error
D912 - D917
Transmit Data
D918 - D923
Receive Data
D8071
Communication Error
D924 - D929
Transmit Data
D930 - D935
Receive Data
D8072
Communication Error
D936 - D941
Transmit Data
D942 - D947
Receive Data
D8098
Communication Error
D1248 - D1253
Transmit Data
D1254 - D1259
Receive Data
D8099
Communication Error
D1260 - D1265
Transmit Data
D1266 - D1271
Receive Data
Slave Stations
D8069
Communication Error
Slave Station 1
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 2
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 3
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 4
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 30
D900 - D905
Transmit Data
D906 - D911
Receive Data
D8069
Communication Error
Slave Station 31
D900 - D905
Transmit Data
D906 - D911
Receive Data
Note:
When data link is used on port 3 through port 7, data link communication error codes are stored in the consecutive data regis-
ters starting from the data register designated in Function Area Settings.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]