13: T
ROUBLESHOOTING
13-2
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
3.
On the right of the Error Status in the PLC Status dialog box, click the
Details
button.
The PLC Error Status screen appears.
Clearing Error Codes from WindLDR
After removing the cause of the error, clear the error code using the following procedure:
1.
From the WindLDR menu bar, select
Online
>
Monitor
>
Monitor
. The monitor mode is enabled.
2.
From the WindLDR menu bar, select
Online
>
Status
. The PLC Status dialog box appears.
3.
On the right of the
Error Status
in the PLC Status dialog box, click the
Clear
button.
This procedure clears the error code from special data register D8005 (general error code), and the error is cleared from
the PLC Status dialog box.
Error Cleared
Clear Button