Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
16
of 84
2.
Carefully align each Power Module with the internal chassis guides.
3.
Firmly push into the system back plane until the module latch clicks,
and the module is flush with the unit’s front panel.
NOTE: The Power Modules can be easily removed by pressing the release
latch to the right while firmly pulling the module from the unit (the
system may be powered while swapping modules). The latch is
located under the module handle (see Figure 11).
4.
Install an optional blanking plate (ICT-BPM) into any unused Power
Module positions to prevent accidental access to the internal
circuitry of the system.
2.12
System Wiring Final Verification
1.
Connect a 10/100 Base-T Ethernet cable to the RJ45 LAN port on
the rear panel to allow for remote monitoring and control of the unit.
NOTE: See the Network Monitoring and Control section for information on
configuring and using the built in GUI, e-mail, or SNMP functions
(Section 4.8.2).
2.
Check that all connections to the power supply are correct and
properly tightened.
3.
Install the protective bus bar cover(s) using the screws provided.
2.13
AC Power Source Connections
WARNING
AC input wiring to the Hybrid Ultra unit must be protected using
an outlet with a branch rated circuit breaker of 30 amps or lower
value.
CAUTION
Install appropriately rated surge suppression systems on AC,
DC, and data connections.
The ICT Hybrid Ultra provides flexible, managed DC power from single-
phase AC power between 100- and 300-volt AC.
1.
Create an AC power cable using a 3-conductor cord rated for the
maximum input current of the unit (up to 27 amps) by stripping and
terminating the three wires in the Line, Neutral, and Ground
terminals of the removable AC input connector provided with the
unit (AC line labeled "L", neutral labeled "N" and safety ground to
the middle pin).