DISCHARGE TEST (only available for lead-acid batteries):
Configure
the "Battery Discharge Test" to check on the battery’s ability to power the
system for a set duration. Set Max Discharge Time, minimum Stop
Voltage, and the automatic repeat interval if desired. Each time the test
is run the output voltage from the Power Modules will be reduced so that
the external battery will power the system load until either the MAX TIME
limit or the STOP VOLTAGE is reached.
A Discharge Test Complete notification (on the front display and with an
e-mail if messaging is configured via the GUI) will indicate a Test Failure
if the Stop Voltage is reached before the Max Time limit, as the battery
was not able to power the load for the desired duration. The unit’s data
log (see Section 4.8.1) will record the completion of the discharge test
while a pop-up window will appear on the front display screen (see
Section 3.2.8).