The DC-DC Converter Module provides up to 700 watts output power which
is drawn from the Hybrid Ultra’s primary voltage bus. The max current rating
is shown in Table 9.
Table 9. DC-DC Converter Module Output Capacity
Converter Voltage
Converter Output Capacity
12 V
50 A
24 V
25 A
CAUTION
•
Ensure that the current draw on the DC-DC Converter
Module output does not exceed the output capacity.
•
Incorrect wiring may damage both the converter and any
equipment attached.
2.9
Battery Connections
WARNING
Risk of serious personal injury or damage to equipment and
property. Observe the following:
•
Use a battery with rating and capacity appropriate for the
model of power supply in use.
•
Use an appropriate DC overcurrent protection device in line
with the backup battery connection.
•
Use wire and connectors rated for the maximum load
current.
•
Ensure battery polarity is correct before connecting.
•
Do not attempt to charge a frozen battery.
•
Always install batteries in well-ventilated areas.
•
Handle batteries with care, never short circuit battery
terminals.
•
Always consult with battery manufacturer and observe all
battery manufacturer recommendations.
•
When connecting a battery, ensure the nominal battery
voltage is correct, and that the battery positive is connected
to a positive terminal and the battery negative is connected
to a negative terminal.
•
Note that the BAT terminal on the BMMD is internally tied to
either the (+) or (−) system output through the LVD
contactor, depending on the polarity of the power system
used.
•
Check system model polarity before connecting a battery to
the BMMD.