Module Output Control
Each output on the LDM will be displayed with name and status. A green
Enabled indicates the electronic relay on that output channel is closed or
turned on. A red Disabled indicates that the electronic relay is open or
turned off (Enabled or Disabled).
Select the
"On" or "Off" buttons to turn the output on or off. This will not
affect the mechanical circuit breaker. The default setting is Enabled.
Master Output Control
Select "All Outputs On" or "All Outputs Off" to turn on or off all four output
channels simultaneously. The default setting is Enabled.
Module Setup
Power-On Sequencing / Power Cycling
Delay Time
: Set the time in seconds (0–60 seconds) that will be used
as the delay between energizing outputs. Will affect all outputs. Set to 0
to disable. Use this feature to allow a delay between energizing specified
loads to reduce inrush current. The default setting is 0 (Disabled).
Alarm Reporting
Activate Alarm Form C Contact:
Select the check box to have the rear
panel alarm contacts change state for an alarm condition. The default
setting is Disabled.
Send E-mail:
Select the check box to have an e-mail sent to the e-mail
addresses set up on the communications page for an alarm condition
(see Section 4.8.3). The default setting is Disabled.