Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
21
of 84
3.2.1
System Status
The main system status screen will show the most current operating
conditions for the unit, primarily the Input Voltage (VAC), the Output Voltage
(VDC), and the total Output Current (A).
Other information will be shown depending on the operating state of the unit:
•
A small thermometer symbol to indicate that the remote
temperature sensor is installed and may be compensating the
output voltage
•
A bar graph indicating relative output current
•
Indication that the output has been disabled (off)
•
Indication that a battery discharge test is in process
•
The Output Current will flash if the unit is operating at the set
Current Limit.
Press Enter to move to the System Settings.
System Settings
The Output Voltage and Output Current Limit settings come with factory
default values that should be adjusted to match the actual system and
battery float voltage requirements, as shown below:
Scroll to highlight the parameter to change.
•
System Voltage
•
Max total Output Current Limit
•
Output Enable ON/OFF (default = ON)
•
Advanced Options (see Section 3.2.7)
Press Enter to select.
Use the Up/Down buttons to adjust setting
(Output Voltage shown), press Enter to
set value and return to previous screen.
Press Back
X
to return to System Settings
screen without saving changes.
NOTE: The output voltage and current limit settings apply to the combined
output of all installed Power Modules. The ICM treats the combined
modules as a single high-power supply. Adjust the system Output