Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
40
of 84
Run-time Remaining:
Shows the estimated time in hours and minutes
before the battery is discharged. This is blank if the batteries are
charging. Only displayed when the unit is configured for lead-acid
batteries.
Battery State of Charge:
Shows the estimated state of charge in %.
The system resets the SOC to 100% whenever it detects that the battery
is at the rated Float Voltage with minimal charge current for at least 24
hr. Only displayed when the unit is configured for lead-acid batteries.
Battery 2 Voltage:
Shows the voltage of battery #2. This field only
displays when a BMMD is installed.
Alarm Status
: Shows status of the batteries (Alarm or OK).
12/24V DC Converter
This section will show the status of the Integrated DC-DC Converter Module
— section will be labelled with the module number and output voltage of the
DC-DC Converter Module.
Output Voltage:
Shows the output voltage of the Integrated DC-DC
Converter Module.
Output Current:
Shows the output current of the Integrated DC-DC
Converter Module.
Output Status:
Shows the status of the output of the Integrated DC-DC
Converter Module. Will show Enabled if providing output or Disabled if
not.
Alarm Status:
Shows status of the DC-DC Converter Module (Alarm or
OK).
Load Distribution
This section will show the status of the four LDM outputs; the section will be
labelled with the module number.
Output #x
: Shows name and status of the output. Will show amps of
current being drawn. Will show OPEN if the breaker is turned off or has
tripped due to an overcurrent event. Will show OFF if the output is
disabled in the GUI.
Alarm Status
: Shows status of the LDM. (Current, Alarm or OK).